Search

Mobile Website

安华电气

Fax:0511-88450870
Mobile:18905289318
E-mail :
anhua@zj-ace.com
Address:The Economic Development Zone

of Yangzhong City,Jiangsu Province

0511-88450870

Copyright ©  Zhenjiang Anhua Electric Co., Ltd ALL RIGHTS RESERVED

Advisory service hotline:

Contact us

Products
>
>
>
KYN28-12 Metal armored removable switchgear
Name

KYN28-12 Metal armored removable switchgear

Affiliate classification
没有此类产品
Detail

Overview

KYN28-12 (Gzs1-12) metal armored switch-type switchgear (hereinafter referred to as switchgear) is the joint design of the Longyuan Electric Power Research Institute commissioned by the former Ministry of Electric Power. The product should be developed by the majority of power users and design units. Cheng, the product is in line with national conditions, has high technical indicators, can be applied to the development of the power market, and can compete with existing imported products. This product is suitable for 3~12KV three-phase AC 50HZ single busbar and double busbar segmentation system for receiving and distributing electric energy.

This product complies with EC298 international electrical standard and GB3906 national standard and DL402, DL403, DL404 power department index requirements, has reliable "five-proof" function, high structural strength, reasonable device layout, complete program, strong scalability, is a kind The ideal new power distribution unit has been widely used.

 

Model meaning

pic

 

Use environment

The ambient temperature is not higher than +40 ° C, not lower than -10 ° C, and the average temperature within 24 hours is not higher than +35 ° C.

The altitude is no more than 1500 meters.

The daily average relative humidity is not more than 95%, and the monthly average relative humidity is not more than 90%.

Equipment should be installed in locations where there are no cracks and shocks, and where electrical components are not subject to corrosion.

The installation of the equipment and the inclination of the ground does not exceed 5 degrees.

Users can negotiate with the manufacturer if they have special requirements.

 

Technical data
 
pic

 

 

Structural features

The switch cabinet is composed of two parts: a cabinet and a handcart. The cabinet is assembled by bolts, and the outer casing and the inner partition are made of aluminum-zinc plate. The cabinet consists of four different functional units: the handcart room, the busbar room, the cable room, and the low pressure room. The removable unit can be divided into: circuit breaker handcart, voltage transformer handcart, isolation handcart, metering handcar, fuse handcart, lightning arrester handcart, etc. according to the use.

Guide rails are installed in the handcart compartment to ensure that the handcart moves in a balanced and reliable manner within the cabinet. The metal shutters are automatically opened and closed by the hand truck, and the upper and lower shutters can be opened separately for easy maintenance and safety. The handcart door is closed and the handcart can be moved. The position of the handcart and the indication and energy storage indication of the circuit breaker can be observed through the inspection window.

The cable room can be equipped with current transformers, voltage transformers, earthing switches, lightning arresters, zero-sequence transformers, sensors, etc. The cable connection height is above 650mm, and the single-core cable can connect up to six at each phase.

The busbar room is insulated by busbars, and the adjacent busbar compartments are separated by wall bushings, which can effectively prevent accidents from spreading. According to the rated current, the main busbars can be used with 1~3 copper bars.

The door panel and the internal mounting plate of the low-voltage room can be installed with various secondary equipment according to different requirements. The control busbar is installed on the top plate of the low-voltage room and covered with a rotatable partition to facilitate on-site installation.

A pressure release device is arranged above the handcart room, the busbar room and the cable room. When an arc occurs in the cabinet, the device can release the pressure and discharge the gas when the air pressure rises, thereby ensuring the safety of the operator and the switchgear.

The switchgear has a reliable interlocking device, which fundamentally prevents the harm caused by misoperation, and effectively ensures the safety of the operator and the switchgear. When the switchgear performs the following operations, the associated lock condition must be met, otherwise the operation will be prohibited.

The handcart enters the working position from the test position: the position of the circuit breaker "minute" and the position of the grounding switch "minute"

The handcart retreats from the working position to the test position: the circuit breaker "minute" position

Breaking and closing of the circuit breaker: the handcart is locked in the working position or test position

Split grounding switch: handcart locked in test position

Open the cable compartment door: the grounding switch "closed" position

Plug and unplug the secondary plug: the handcart is locked in the test position

 

Download Google

The user provides the following information:

1. One main wiring plan diagram and main bus type specifications;

2. The secondary schematic diagram and terminal diagram of each cabinet;

3. Secondary small busbar layout and small busbar form;

4. Distribution room layout plan and related sectional drawings;

5. If a busbar bridge (busbar bridge between walls or busbar bridges between walls) is required, span and height gauges are required;

6. Summary table of electrical equipment;

7. Color-coded code or template for surface coating;

8. Regional special requirements and special use environment shall be submitted at the time of ordering;

9. Types and quantities of accessories and spare parts that need other or excess.

 

 

Installation diagram

 

pic

 

Floor opening diagram

 

pic

Corresponding parameter set not found, please add it in property template of background
暂未实现,敬请期待
暂未实现,敬请期待
Previous article